TABmaster Airflow Capture Hood Model 6710
Durable capture hood for direct supply and return airflow measurement, with temperature, humidity, direction indication and 3,000-record storage.
Products
| Model | Group | Positioning | Core fit |
|---|---|---|---|
| 6710 | Airflow capture hood | Direct air-volume measurement at registers, grilles and diffusers | HVAC balancing, commissioning and periodic verification |
Key Features
Direct air-volume measurement
Capture supply or return airflow without performing a point-by-point traverse.
Multi-parameter display
Shows airflow, temperature, humidity and flow direction.
Interchangeable hood sizes
Optional hood frames adapt the instrument to common diffuser and grille dimensions.
Organized data storage
Stores up to 3,000 measurements and groups records under job or location IDs.
Technical Specifications
| Parameter | Unit | Value / Description |
|---|---|---|
| MEASUREMENT | ||
| Airflow range | m³/h | 40–4,300 |
| Airflow accuracy | — | ±3% of reading ±8 m³/h above 85 m³/h |
| Resolution | m³/h | 1 |
| Temperature range | °C | 0–50 |
| Humidity range | %RH | 0–100 |
| GENERAL | ||
| Standard hood | mm | 610 × 610 |
| Data memory | measurements | Up to 3,000 |
| Interface | — | USB |
| Available hoods | — | Multiple optional sizes for common outlets |
Values shown are manufacturer specifications or documented configuration details. Confirm final model, probe, accessories, regional availability and calibration scope before ordering.
Applications
Supply and return balancing
Measure air volume directly at ceiling and wall outlets.
Design-flow verification
Compare measured terminal flow with the system schedule.
Terminal airflow checks
Measure supply volumes where the hood and procedure are appropriate.
Seasonal performance checks
Track changes in terminal airflow after service or filter replacement.